|
New Electronic Controls Package
AERCO has combined the speed and performance of an electronic actuator with the precision and convenience of a digital controller as a standard controls package available with all its steam-to-water and water-to-water heaters.
Faster & More Accurate
Reliable Under Fluctuating Loads
Fail-safe Auto Shutdown
Remote Access
Full Integration to BAS Software
Easy, One Touch, Start-up
Available for all AERCO indirect-fired products
For the first time ever, this package allows facility managers to read real time flow rates.
Robust Support for a Wide Variety of Operating Conditions
| Temperature set point range: |
50°F to 205°F |
| Max. Working Pressure: |
235 PSIG @ 400°F |
| Sat. Steam Operation: |
5 to 150 PSIG @ 365°F |
| Boiler Water Operation: |
160 PSIG @ 300°F |
| Pressure/Temp. Relief Valve: |
150 PSIG/210°F |
| Size Range: |
1 1Ό 1½ 2 2½ 3 4 |
| End Connection: |
|
| - NPT |
1 to 2 |
| - ANSI Flange (150#) |
2½ to 4 |
| Power configurations: |
120V/1 Phase/60Hz |
| |
220V/1 Phase/50 Hz |
Fast & Precise Control Under Fluctuating Loads
AERCOs electronic controls package maintains ±2°F temperature control when units are operated under constant load conditions and deliver ±4°F temperature control under normal load changes.
The secret to the outstanding performance of the control package can be found in the AERCO valve. The patented design employs a pilot assembly, balanced lower piston design, equal percentage plug and soft seat for fast and accurate, response. Despite 1 to 100% rangeability, it takes less than 7 seconds for a 1-2 valve to reach full-open, full-close or failsafe shutdown position. And it takes just 9 seconds for full actuation of a 2½-4 valve. Mouse over picture at left for more info.
Fully Compatible with BAS Systems
For facilities seeking LEEDs accreditation points and those that have taken a building-wide approach to energy efficiency, the electronic controls package supports easy integration with Energy Management Software (EMS) and Building Automation Software (BAS) programs. Using an optional add-in board which supports Modbus communications, customers can centrally monitor and/or control the heater via an RS-232 or RS-485 connection. A standards-based open protocol used throughout the building-controls market, Modbus integration offers a communications gateway to control and/or poll important operating parameters of the heater including those listed at left. AERCO also offers a Communications Gateway to support BACnet, LonWorks and N2 system integration for units equipped with the Modbus board.
Digital Controller Simplifies Start-Up and Control
Operating parameters for the heater are entered directly to the digital controller. Just set and go without the hassle of manually adjusting components associated with pneumatic-based control solutions. The electronic package incorporates both feed-forward and feedback features which enable users to tune operations in real time. Both the steam-to-water and water-to-water controller interfaces are protected by a clear cover which can be locked to discourage unauthorized changes to operating parameters. The power switch for the unit (not pictured) is located on the exterior right side of the controller.
Mouse over pictures at left for more info.
Integrated Safety Shut-Off Streamlines Installation
With AERCO equipment, customers no longer must worry about purchasing and installing ancillary parts to support the water heater. The electronic controls package design incorporates an integrated safety system to close the control valve and open the solenoid to dump water in the event of an over-temperature condition. This fail-safe mechanism also protects customers in the event of a power loss at the facility.
Available with these AERCO Heaters
WaterWizard High-Efficiency Heater
A-Plus Steam-to-Water Heater
B-Plus Steam-to-Water Heater
E-Plus Water-to-Water Heater
Full Line of Steam to-Water Double Wall Heaters
Full Line of Water-to-Water Double Wall Heaters

|